Monitoring and maintenance of liquid cooling loops
After go-live, we monitor temperature, pressure, flow and leaks, and we maintain the loop for the life of the system: preventive maintenance, water analysis and on-call support.
A loop is not finished on the day it starts.
A closed loop changes over time. The corrosion inhibitor is consumed, warm water favours bacterial growth, filters load up, air collects at high points. None of this is visible from the data hall until a temperature rises or a flow drops.
Monitoring and maintenance keep the loop in the state it had at handover, and keep the proof of it.
What we monitor
- Temperature, pressure and flowReported to your BMS.
- LeaksZoned leak detection, with isolation rack by rack.
- Fluid chemistryFollowed over time against your thresholds and the manufacturer's.
Maintenance contract
3 building blocks, to combine.
Preventive maintenance
Pressure drop across filters, air venting, joints and supports, calibration of sensors.
Water analysis
pH, conductivity, glycol and inhibitor concentration, bacterial count, against your thresholds and the hardware manufacturer's.
On-call support
A response time fixed in the contract. For a leak or a hose damaged during handling: lockout, repair and a traced refill. A stock of spare parts is sized with you.
For operators, and for cooling manufacturers.
Directly for the operator
AI clouds and enterprise data centers can entrust us with the loop after go-live. On a loop we delivered, the team that maintains it knows how it was designed, built and commissioned.
As the manufacturer's local second line
Cooling manufacturers can rely on us as a local partner for the maintenance of their installed equipment in Europe.
Questions about maintenance.
What does liquid cooling maintenance include?
3 building blocks that can be combined: preventive maintenance of the loop (pressure drop across filters, air venting, joints and supports, sensor calibration), water analysis (pH, conductivity, glycol and inhibitor concentration, bacterial count) and on-call support with a response time fixed in the contract.
Why does the coolant need to be analysed over time?
In a closed loop, the corrosion inhibitor is consumed and warm water favours bacterial growth. Regular analysis of pH, conductivity, glycol and inhibitor concentration and bacterial count shows drift early, before it damages the cold plates or reduces the flow.
What happens if there is a leak?
The on-call team intervenes within the response time fixed in the contract: the affected section is locked out, repaired, then refilled, and the refill is traced. A stock of spare parts is sized with the client in advance.
A loop to keep in specification?
Tell us about your installation and your service levels. We build the contract from the 3 building blocks.